SteelCrete Access Floor for Data Center
Access floor panels with factory-bonded HPL Finishes have become the standard in Data Center because of its ease of maintenance and its unique ability to dissipate static electricity. For strictly static sensitive applications, access floor panels with factory-bonded Vinyl Finishes are better choices.
 
HPL/Vinyl Finished SteelCrete Panel + Perforated Panel + Bolted Stringer System
Dimension: 600mm x 600mm or 24'' x 24''.
SteelCrete panel grades: SC800, SC1000, SC1250.
Wide range of HPL/Vinyl Finishes.
Finished floor heights: 150mm ~ 1200mm.
PVC taped rectangular stringer provides excellent loading and air-tightness performance.
 
Dowseng® SteelCrete Access Floor is Zinc Whisker Free.
HPL Finished SteelCrete Access Floor Performance Chart
General Information
Static Loads
Rolling Loads
Impact
Loads
SteelCrete
Panel
Understructure
System
Weight
Concentrated
Loads
Ultimate
Loads
Uniform
Loads
10
Passes
10,000
Passes
SC800H
Bolted
Stringer
9.6lbs/ft²
46kg/m²
800lbs
363kg
2400lbs
1089kg
300lbs/ft²
14.35kPa
600lbs
272kg
400lbs
182kg
150lbs
68kg
SC1000H
Bolted
Stringer
10.2lbs/ft²
49kg/m²
1000lbs
454kg
3000lbs
1363kg
350lbs/ft²
16.75kPa
800lbs
363kg
600lbs
272kg
150lbs
68kg
SC1250H
Bolted
Stringer
10.8lbs/ft²
52kg/m²
1250lbs
567kg
3750lbs
1701kg
400lbs/ft²
19.1kPa
1000lbs
454kg
800lbs
363kg
150lbs
68kg
Vinyl Finished SteelCrete Access Floor Performance Chart
General Information
Static Loads
Rolling Loads
Impact
Loads
SteelCrete
Panel
Understructure
System
Weight
Concentrated
Loads
Ultimate
Loads
Uniform
Loads
10
Passes
10,000
Passes
SC800V
Bolted
Stringer
10.0lbs/ft²
48kg/m²
800lbs
363kg
2400lbs
1089kg
300lbs/ft²
14.35kPa
600lbs
272kg
400lbs
182kg
150lbs
68kg
SC1000V
Bolted
Stringer
10.6lbs/ft²
51kg/m²
1000lbs
454kg
3000lbs
1363kg
350lbs/ft²
16.75kPa
800lbs
363kg
600lbs
272kg
150lbs
68kg
SC1250V
Bolted
Stringer
11.2lbs/ft²
54kg/m²
1250lbs
567kg
3750lbs
1701kg
400lbs/ft²
19.1kPa
1000lbs
454kg
800lbs
363kg
150lbs
68kg
Perforated Panel For SteelCrete Access Floor
Perforated panel is specially constructed to allow for air flow distribution from under the raised access floor. In today's data center design, 45% airflow rate of perforated panel is the minimum requirement.
 
Bare/HPL/Vinyl Finished Perforated Steel Panel
Dimension: 600mm x 600mm or 24'' x 24''.
Perforated panel airflow rate 50%.
Perforated panel grades: PERF1000, PERF1250.
Wide range of HPL/Vinyl Finishes.
SteelCrete Perforated Panel Performance Chart
General Information
Static Loads
Rolling Loads
Impact
Loads
Perforated
Panel
Understructure
System
Weight
Concentrated
Loads
Ultimate
Loads
Uniform
Loads
10
Passes
10,000
Passes
PERF1000
Bolted
Stringer
6.7lbs/ft²
32kg/m²
1000lbs
454kg
3000lbs
1363kg
350lbs/ft²
16.75kPa
Not Recommended
150lbs
68kg
Aesthetical And Functional Finishes
HPL And Vinyl Finishes
One of the advantages of a raised access floors is that it is fitted dry to overcome any difficulties on the building’s floor slab. By offering a wide variety of Aesthetical And Functional Finishes, it is an extremely versatile system which gives the designer great freedom of action.